Merz Price Differential Protection for Transformer Explanation | Electrical4u (2024)

Merz Price Differential Protection for Transformer:

Merz price differential protection is used to protect the transformer from internal short circuit, Internal ground faults and inter turn shorts. Transformer is a static device. Merz price differential protection is nothing but a percentage differential protection Which works under the principle of circulating current scheme.

Merz Price Differential Protection Working Principle:

The two ends of the transformer both primary and secondary are connected with the current transformer. The output of the current transformer is given as shown in the figure.

In that, the relay operating coil A, B, and C are connected with respect to each phase and the CT neutral terminal. Here the vector sum of the current of each phase is equal to zero, hence the net current through the relay operating coils A, B and C is zero.

The relay becomes inoperative. During the abnormal condition, the current flow in both sides of CT becomes unequal.

Learn More: How to Calculate Stabilizing Resistor for High Impedance Differential Protection

Therefore, the unbalance current flows in the relay operating coil. if the current in the relay operating coil is higher than the pickup value of the relay, then the relay sends the trip command to the circuit breaker.

Conditions for Transformer differential protection:

While using these circulating current transformer protection, the following condition must be fulfilled.

CT ratio:

For percentage differential protection or normal differential protection, the Current transformer ratio in the primary and secondary winding should be the same.

But in the power transformer, we use it as either step-down or step up the voltage. So that always the current in the primary and secondary will be unequal. Hence the relay operates the circuit breaker even there is no fault.

This CT ratio will be eliminated by adding an interposing current transformer. The interposing current transformer matches the current between the primary and secondary CTs. It is connected to the star connection side of the current transformer.

Learn More: Trip Circuit Supervision TCS Relay Working Function and Operation

Another method, that you can compensate for the difference in the magnitude of currents in the primary and secondary power transformer by matching their turns ratio of the low voltage winding.

Consider, K is the turn-ratio of the power transformer, then you can match the difference by the turn ratio of CTs on the l.v. the side is made K times that of the CTs on the h.v. side.

For example, Take a power transformer with a voltage of 110 kV/11kV. From that, you can calculate the turns ratio of 10. Now you are using CT of 200/1 on the high voltage side.

Hence the CT ratio becomes 200. For that, you have to use 2000/1 CT on the secondary side to match the magnitude of the current.

If you follow the above two, the secondary of the two CTs will carry equal currents under normal load conditions. Consequently, no differential current will flow through the relay and it remains inoperative.

Learn More: CT Supervision Relay Working Principle

Transformer Phase shift:

In a Power or distribution transformer, there is usually a phase difference between the primary and secondary currents of a 3-phase power transformer.

This exact angle of phase shift is mentioned in the transformer’s nameplate details. Even, if you use proper turn-ratio, a differential current may flow through the relay under normal conditions and cause relay operation.

This phase shift can be overcome by connecting the CTs in the opposite configurations. Typically, if the transformer winding is star connected then you should use CT as delta connection, like that for delta connected winding you should use star connection of CT secondary.

Please refer to the table that you can help you for various type of transformer connection and their respective CT connection.

Tappings of the transformer:

Mostly power transformers use an on-load tap changer for adjusting the voltage level to constant. Hence the change in the voltage level affects the secondary current in the transformer.

Learn More: No Volt Release (NVR) and No Voltage Relay Working Principle

If you increase the voltage level, the current becomes reduced, and vice versa. This tapping creates an unequal current in the CT secondary. Therefore, the relay starts malfunctioning.

To overcome this, the current transformer contains tapping on its secondary side. The tappings are being adjusted according to the voltage changes in the transformer. But it is practically not possible.

Effect of Magnetizing inrush current:

Magnetizing inrush current is nothing but a current which flows when you energize the transformer. Since starting the transformer has zero induced emf in the windings.

This current only comes in primary of the current transformer. It is very short and but heavy (app. 4 times of the transformer full load current) Therefore, this inrush current leads to relay misoperation.

Magnetizing inrush current misoperation can be easily resolved. Magnetic inrush current has more second harmonic current of approximately 70%.

Therefore, we can design a relay with only operates in fundamental components. However, it reduces the sensitivity of the relay.

Learn More: Primary and Backup Protection Working Principle

Length of the pilot wire:

The pilot wire is nothing but a looping wire which is used to connect the CT and relay panel. Generally, a power transformer will be placed in the switchyard.

Which would be far away from the control panel. To connect and bring the Current transformer’s output from the switchyard, the cables are used.

These cables are called pilot wires. Change in the length of the pilot wire, which affects the performance of the relay.

To overcome this issue, we have to calculate the total resistance of the pilot wire. After calculating the resistance value, we have to match them by connecting the adjustable resistor.

By adjusting the value of resistance, the restraining and operating become balanced or balance to be done.

Key Concept of Merz price protection:

While applying the circulating current principle for protecting the power transformer or distribution transformer we should fulfill the above 5 conditions avoid inadvertent relay operation.

Learn More: SWG to Current (amperage) Chart - Transformer Wire Amperage Table

Example:

A 3-phase transformer having a line-voltage ratio of 0·4 kV/11kV is connected in
star-delta and protective transformers on the 400 V side have a current ratio of 500/5. What must bethe ratio of the protective transformers on the 11 kV side ?

Solution:

For star/delta transformers, CTs will beconnected in delta on 400 V side (i.e. star side of power transformer) and in star on 11,000 V side (i.e.delta side of power transformer).

Video Explanation In English of differential protection for transformer:

Video Has Taken under section 101 fair & education usage act.

Also see:

  • Merz Price Differential Protection for Generators
  • Neutral Voltage Protection -59GN- 95% stator Earth fault protection
  • CVT in Electrical Capacitive Voltage Transformer CVT
  • Droop CT – Droop Current Transformer
  • How to Read CT Current Transformer Nameplate Details
  • Potential Transformer Working Principle
  • Relationship of Frequency Vs KVA Output or Rating of Transformer
  • Three Phase Transformer Vector Grouping Significance of Vector Grouping
  • Transformer Bushing Operating Principle
  • Transformer Core Construction Details
  • Trip Circuit Supervision TCS Relay Working Function and Operation
Learn More: Over Voltage Protection Working Principle 59
Merz Price Differential Protection for Transformer Explanation | Electrical4u (2024)

FAQs

What is Merz Price protection of transformers? ›

Merz Price protection is a percentage differential protection scheme used for the protection of power transformers from internal faults like short circuits, ground faults, and inter-turn faults.

How does transformer differential protection work? ›

The differential relay compares the primary current and secondary current of the power transformer. If the primary current and secondary current are found to be unbalanced, the relay will start the primary and secondary circuit breakers of the transformer and trip each other.

What is the Merz Prize circulating current principle? ›

The difference of the currents under fault conditions is arranged to pass through the operating coil of the relay. The relay then closes its contacts to isolate protected section from the system. This form of protection is also known as Merz-Price circulating current scheme.

Why is Merz Price protection not suitable beyond 33kV? ›

Why Merz-Price Protection is not suitable beyond 33kV? Difficulties are experienced in balancing the secondaries of the CTs and this is why Merz-Price protection is not employed beyond 33kV.

What are the disadvantages of Merz price voltage balance system? ›

Limitation of Merz Price Protection of Alternator

CT Saturation: During severe faults, the current transformers may saturate, leading to inaccurate current measurements and potential failure to detect the fault.

What is the basic principle of the differential scheme of protection? ›

Differential protection is a type of protection scheme used in power systems to protect generators, transformers, and feeders. This protection principle is based on the comparison of the current entering and leaving the protected equipment.

What are the disadvantages of differential protection of transformer? ›

Differential protection has several advantages, but it also has some drawbacks and limitations that need to be taken into account. These include errors and malfunctions due to CT saturation, ratio mismatch, phase displacement, or external faults with CT failure or incorrect polarity.

What is the concept of differential protection? ›

In any closed circuit, the current exiting and entering the power supply must be equal. Differential current protection, much like a ground-fault interrupter (GFI), measures incoming and exiting current from all three phases, stopping the circuit in case of any imbalance, no matter how long it persists.

What is the percentage of differential protection for transformers? ›

Percentage Biased Differential Protection

These are the minimum pick-up and the slope. The minimum pick-up covers the transformer magnetizing current, typically 1-4% of the transformer rating. A pick-up of 0.2 to 0.3 times the TAP is generally recommended.

What is the principle of circulating current differential protection? ›

With the circulating current principle, restraint current flows through the pilot wire loop and prevents relay pick-up during load and external faults. During an internal fault, the restraining pilot current is reduced and allows tripping.

How does circulating current work? ›

Circulating currents are flowing electrical currents that occur in electric motors as a result of imbalances in the motor and the voltage it creates between the stator and rotor iron. These imbalances create an asymmetrical magnetic field in the motor.

What is the principle of over current? ›

Working Principle: When the current in an overcurrent relay exceeds a critical level, the magnetic effect of the coil activates the moving element, altering the relay's contact position.

What is another name for Merz price protection? ›

Merz price protection is also called differential protection. For alternator, the most severe outcome of fault is the damage of stator.

How does a Buchholz relay work in a transformer? ›

Working of Buchholz relay:

Whenever a minor fault occurs inside the transformer, heat is produced by the fault currents. The produced heat causes the decomposition of transformer oil and gas bubbles are produced. These gas bubbles flow in the upward direction and get collected in the Buchholz relay.

What are the problems associated with differential protection relays? ›

Differential relays have faced challenges such as failure to detect the inrush current, inappropriate performance in high second harmonic faults, and maloperation when the current signal becomes noisy.

What are the protections for transformer? ›

Transformer protection can be broadly categorized as electrical protection implemented by sensing mainly the current through it, but also voltage and frequency and, as mechanical protection implemented by sensing operational parameters like oil pressure/ level, gas evolved, oil & winding temperature.

What is the fire protection of transformers? ›

Indoor Guide for Transformer Fire Safety Practices

Dry-type transformers should be used inside buildings whenever possible. If an oil-insulated transformer with over 100 gallons of oil is used inside, it must be separated by a fire wall with a three-hour fire resistance rating.

What is protection for current transformers? ›

Protection current transformers are used to control protective relays that have the role of disconnecting downstream circuits in the event of a current surge. Proportional transmission behaviour of the transformer up to a multiple of the nominal current is required for the reliable function of this relay.

How does busbar protection work? ›

Busbar protection uses differential protection to isolate faults on the busbar. It works by comparing the current entering and leaving the busbar using CTs - any difference indicates an internal fault.

Top Articles
Latest Posts
Article information

Author: Fr. Dewey Fisher

Last Updated:

Views: 6120

Rating: 4.1 / 5 (62 voted)

Reviews: 85% of readers found this page helpful

Author information

Name: Fr. Dewey Fisher

Birthday: 1993-03-26

Address: 917 Hyun Views, Rogahnmouth, KY 91013-8827

Phone: +5938540192553

Job: Administration Developer

Hobby: Embroidery, Horseback riding, Juggling, Urban exploration, Skiing, Cycling, Handball

Introduction: My name is Fr. Dewey Fisher, I am a powerful, open, faithful, combative, spotless, faithful, fair person who loves writing and wants to share my knowledge and understanding with you.